Overview
ScaleStop Physical Water
Conditioner is for treatment of hard water and the reduction of
limescale in domestic water services.
For Dwellings -
Commercial Premises -
Process Water
- No Salts
- No Chemicals
- No Electricity
- No Servicing
- No Waste
- Fully Potable Water
- WRAS approved
- Highest Scoring Effectiveness
of any PWC
ScaleStop System
ScaleStop comprises a pressure vessel partially
filled with a media through which the cold water supply is passed
using simple inlet and outlet connections. The vessel is bottom
fed so that it fluidises the media bed.

Sub microscopic particles of scale
form spontaneously in the water due to the media and remain suspended
as it flows from the vessel. When the water is later heated, the
same particles act as highly efficient nucleation seeds for the
formation of further scale, thus stopping it encrusting surfaces.
As well as minimising scale encrustation, ScaleStop is also capable
of removing existing encrusted deposits.
Efficiency
ScaleStop is extraordinarily efficient
because it requires no electrical power, magnets or other form
of energy. It consumes no chemicals or additives and it generates
no waste. It is self re-generating and completely self contained.
Maintenance and Servicing
There is no requirment for maintenance or servicing under normal mains supply conditions. The life of the media will be determined by the amount of contaminants in the water supply. The media is warranted for a period of two years from the date of installation.
Statutory Compliance
ScaleStop media is WRAS approved.
(0705509).
Effectiveness
The only recognised measure of the
effectivness of PWC's is the German performance test DVGW-W5 12. The result of the test is a score as a percentage reduction of
scaling between treated and untreated heaters. ScaleStop
has achieved a near perfect score of 99.6%.
The pass percentage for W-512 is 80%. None of the PWC's commonly
specified in the UK have passed W-512.
*Further information on W-512 is available here.
Location
ScaleStop vessels should be installed
on the cold water service. Where a break tank is installed, it
is preferable to locate the ScaleStop downstream of the tank and
booster set. Treatment before the tank is acceptable. The vessel must be installed vertically. The treated
water is fully potable.
Sizing
ScaleStop vessels may be installed
as single or as matched multiple united to meet any flow requirements.
There is no minimum flow rate.
The maximum service flow is the maximum
flow at which full treatment effectiveness can be maintained.
Brief periods of higher flows can be accommodated with minimal
impact on performance. Pressure loss at maximum flow rate <
0.1 Bar.
Temperature and Pressure
| Water temperature |
minimum 5°C |
| |
maximum 44°C |
| Water pressure |
minimum 1 bar |
| |
maximum 10 bar |
Water Chemistry Parameters
| Ferrous Iron |
< 300 ppb |
| Manganese |
< 50 ppb |
| Copper |
< 1300 ppb |
| pH |
6.5 to 8.5 |
| Total Hardness (max) |
1,300 ppm |
| Chlorine |
Less than 3 ppm in normal usage but shock treatment is acceptable |
| Chlorine Dioxide |
No limit |