Suggested Specification
An Amalgam Lamp UV System suitable to treat the
maximum (peak) flow-rate of water shall be installed on the water
supply from the Storage tank / on the recirculating water loop.
The UV chamber construction should be of 316L stainless steel
and shall incorporate a UV Sensor responding only to germicidal
wavelengths 250- 260nm. The "L" shaped UV Chamber should
be suitable for horizontal or vertical installation. A separate
UV Control panel providing indication of lamp status, UV Output
and Lamp Hours run shall be provided. UV Dose provided should
exceed 30mWs/cm2 at the end of lamp life.